White paper · Warranty claims · October 2026

Measuring real‑world power loss of UVID‑affected TOPCon modules.

Night drone EL finds UVID; QE quantifies the power each module loses in daylight operation, the figure a warranty claim rests on.Night drone EL finds UVID. Quantified Energy turns those images into the power each module loses in operation, the number a warranty claim needs.

TitleMeasuring Real-World Power Loss of UVID-Affected TOPCon Modules

Night EL image of a TOPCon module, measured 160 minutes after sunset, with many dark cells Same module shifted to its daylight-equivalent state, modeled: dark cells appear lighter
Night EL · 160 min after sunset Daylight-equivalentDaylight state · modeled
20:24

In brief

  • Most new solar modules are TOPCon: about 75% of the solar cells made in 2025[4]. UV-induced degradation (UVID) is a major reliability concern for them[5].
  • UVID causes two losses[1],[2]. The permanent loss stays while the module operates in daylight. The recoverable loss builds up in the dark and recovers in light. In one lab test, a module that lost at most 5.9% in operation appeared to lose 12.2% after time in the dark[1].
  • Drone EL is flown at night and captures both losses in one image. Quantified Energy separates them, so a claim rests on the loss in operation rather than on the night state.
  • Quantified Energy corrects every dark cell to its daylight state with the project's own darkening curve. On the project shown here, the curve came from 9,353 modules flown over four nights, 0.3 to 5.8 h after sunset, and from 20 strings (580 modules) flown both at dusk and at night. Checked cell by cell against the dusk flight of those 580 modules (one array, one night), the corrected cells are right on average and within about 6% of the module's healthy level. The corrected image is then converted to module power[2].
  • The result is each module's loss in operation, split into permanent and recoverable parts. It is checked against lab flash tests on a sample of modules and is ready to compare with nameplate and with the warranted minimum power. This paper covers UVID dark cells only; other defects found in the same survey are assessed under the material warranty.

Abstract TOPCon made up about 75% of cell production in 2025[4]; UV-induced degradation (UVID) is a major reliability concern for it[5]. UVID-affected cells carry a permanent loss and a recoverable loss that builds up in the dark and recovers in light[1],[2]. Drone electroluminescence (EL) is flown at night and records both; separating them is what allows a warranty claim to rest on the loss in operation rather than on the night state. Quantified Energy instead calculates each module's power loss in daylight operation. Cells are normalized to the 90th percentile of their module, and the dark-cell level is fitted against time after sunset (one project: 9,353 night modules over four nights, flown 0.3 to 5.8 h after sunset; r_sun = 0.529, r_∞ = 0.25, τ = 0.84 h). Dusk and night flights of the same 20 strings (580 modules) calibrate the drop from sunset to night: recovering dark cells regain 0.20 ± 0.05 of the healthy level. Each dark cell is lifted toward its sunset level, tapered for cells near the dark threshold, which are often naturally gray, and reduced for the darkest cells, which recover less. Checked cell by cell against the dusk flight of these 580 modules (one array, one night, one dusk pass), the corrected dark-cell levels are unbiased on average (+0.1%) and within about 6% of the healthy level per cell (RMS 5.7%), against −19.0% for the night image as measured. The corrected image is converted to module power with the degradation-mode EL-to-power method[2]; the loss is reported per module, split into permanent and recoverable parts, and benchmarked to flash I-⁠V on a sample of modules. τ differs from lab kinetics[1] and is measured per project. This paper covers the UVID dark-cell step of QE's warranty-claim workflow; other defects found in the same survey are assessed under the material warranty and are out of scope.

Why

UVID adds a recoverable loss in the dark, and night drone EL records it.

Why · The fleet

The fleet is now TOPCon.

PERC led until the move to TOPCon began in mid-2022[1]. By 2025 about 75% of the solar cells made were TOPCon[4], and so were about 95% of the modules shipped by the top-ranked suppliers[6]. TOPCon is expected to stay the main technology for the next decade[4].

PERC led until the shift to TOPCon began in mid-2022[1]. In 2025 TOPCon made up about 75% of crystalline silicon cell production[4] and about 95% of shipments by ranked suppliers[6], and it is expected to remain the leading technology for the next decade[4].

Share of modules shipped · 100 squares = 100%2025 · TOPCon ≈90%

706GW

modules shipped worldwide in 2025[4]

  • ≈90%TOPCon, share of 2025 module shipments[6]
  • ≈10%PERC and other technologies
  • 10 yrTOPCon expected to remain the leading technology; PERC being phased out[4]

Shipment share: InfoLink 2025 ranking, about 95% TOPCon and 1 to 2% PERC among the top-ranked suppliers[6]. The chart rounds TOPCon down to about 90% to allow for smaller suppliers outside the ranking (QE estimate, not a published figure). Cell production share, about 75% TOPCon, and global shipments: ITRPV[4]. The mid-2022 view is illustrative, with PERC still leading as the move to TOPCon began[1].

Shipment share: InfoLink 2025 ranking, TOPCon about 95% and PERC 1 to 2% of shipments by ranked suppliers[6]. The chart rounds this down to about 90% to allow for suppliers outside the ranking (QE estimate, not a published figure). Cell production share, about 75% TOPCon, and global shipments: ITRPV[4]. The mid-2022 view is illustrative, with PERC dominant as the shift to TOPCon began[1].

Why · The risk

UVID is a major reliability concern for TOPCon.

That fleet carries a known risk. UV-induced degradation (UVID) is a power loss caused by the shortest ultraviolet light in sunlight, below 340 nm. Tropical sites receive more of this light, and modules there can show UVID within their first year in the field[1].

UVID is driven by deep UV below 340 nm. Tropical sites receive a higher dose of it and can show UVID within a year of field exposure[1].

UV test · UVID120Lab UV test

3.0%

Median TOPCon power loss after 120 kWh/m² of UVTypical (median) TOPCon power loss after a set lab dose of UV light, 120 kWh/m²[5]

median
015%

Same test · recipe mattersSame test · materials matter

up to14.1%

For one bill of materials; 3.6% for another with cells from the same supplierFor one choice of module materials; 3.6% for another built with cells from the same supplier[5]

14.1%
3.6%
015%

Field · one year

up to8%

Power loss after one year in the field, mainly attributed to UVID; median 2%[5]

max
median
015%

Kiwa PVEL 2026 PV Module Reliability Scorecard[5]. Bars share one scale, 0 to 15% power loss.

Why · Two losses

UVID has a permanent and a recoverable loss.

UVID costs a cell power in two ways[1],[2]. The permanent loss stays while the module operates in daylight. The recoverable loss builds up while the module is in the dark and recovers when light returns the next day[1]. A warranty claim must therefore be built on the loss in operation, which is the permanent loss.

UVID-affected cells carry two loss components[1],[2]. The permanent loss, ΔP_perm, remains in the light-recovered state of daylight operation. The recoverable dark-storage loss, ΔP_rec, builds up in the dark and is recovered by illumination the next day[1]. A warranty claim must rest on the loss in operation.

Schematic · one UVID cell over 48 h permanent · seen in daylightrecoverable · builds up at night

What a claim would see · one module, three states [1]module powerPmax vs 630 W nameplate

Lab EL after dark storage: cells are dim, 553 W Lab EL 1 h after light soaking: cells are bright, 593 W Lab EL after 4 h back in the dark: cells dim again, 583 W
permanent loss recoverable loss 630 Wnameplate 593 W · −5.9%1 h after light 583 W · −7.5%4 h back in the dark 553 W · −12.2%dark storagekept in the dark

Measured in the dark state, the module appears to lose 12.2%; in operation it loses 5.9%[1].

After time in the dark, the module appears to lose 12.2%. In operation, it loses 5.9%[1].

The uncorrected night state roughly doubles the apparent loss · a claim rests on the loss in operation

At most about 37 W lost in operation, not about 77 W · an uncorrected dark reading roughly doubles the loss

Lab EL and flash I-⁠V, SERIS with Quantified Energy[1]. The same TOPCon module, nameplate 630 W, 1 A injection, 15 s exposure; light soaking 1000 Wh/m². The 1 h value after light soaking is taken as the light-recovered state of operation.

Lab data, SERIS with Quantified Energy[1]: EL images and flash power tests of one TOPCon module, nameplate 630 W. After a measured dose of light, 1000 Wh/m², its power 1 h later is taken as its daylight state. The difference from the dark readings is recoverable loss.

20 field modules · each imaged after dark storage and after light soakingeach imaged after time in the dark and after light [2]TOPCon · tropical field exposure

EL of 20 TOPCon modules in two blocks of ten; in each block the upper row is after light soaking and appears bright and even, the lower row is after dark storage and appears darker and patchy
1 to 10 · after light soaking1 to 10 · after light
1 to 10 · after dark storage1 to 10 · after dark
11 to 20 · after light soaking11 to 20 · after light
11 to 20 · after dark storage11 to 20 · after dark

Most of the extra loss seen after time in the dark recovers with lightDark-storage degradation is largely reversible by light soaking[2]

Wide spread of cell damage after time in the dark · a tight group of mildly affected cells after lightBroad, right-skewed after dark storage · narrow peak after light soaking

EL images: [2] Fig. 3, brightness on a log scale. Histogram, re-plotted from [2]: how strongly each cell is degraded, worked out from a single EL image at 6 A of each of the same 20 modules, once after time in the dark and once after light.

EL images: [2] Fig. 3, log intensity scale. Histogram: re-plotted from [2], per-cell degradation severity inferred from a single 6 A EL image of each of the same 20 modules, after dark storage and after light soaking.

Why · Timing

So the measurement time matters.

The recoverable loss starts to build up again as soon as a module is back in the dark[1]. A night drone EL image therefore shows the permanent loss plus part of the recoverable loss, and how much depends on the time since sunset. Left uncorrected, it inflates the loss a claim reports.

Dark-storage loss begins as soon as a light-recovered module is in the dark[1]. Night drone EL therefore records the recoverable loss on top of the permanent loss, by an amount that depends on the time since sunset. Left uncorrected, it inflates the loss a claim would report.

Lab · power lossPmax loss after light recovery [1]module dependent

night drone EL survey window 0%1%2%3% 01234567 hours in the dark after light exposure 1% · 1 h 2.5% · 6 h
daylight night EL permanent + recoverable Schematic · loss seen by EL
up to 1%power loss per day of extended dark storage in UVID-sensitive TOPConpower loss per day of long dark storage, for UVID-sensitive TOPCon[5]

Points: lab values after light recovery[1]; the line only guides the eye. The survey window is indicative.

Points: lab power tests of modules that had recovered in light and were then kept in the dark[1]; the line only guides the eye. The loss keeps growing through the hours of a night survey. The survey window is indicative.

Technical note We call ΔP_perm the UVID loss of Pmax that remains in the light-recovered state, taken as representative of daylight operation, and ΔP_rec(t) the additional dark-storage loss present t hours after local sunset[1],[2]. The loss inferred from night EL is their sum, Eq. (4) in Methods: ΔP(t) = ΔP_perm + ΔP_rec(t), ΔP_rec(t ≤ 0) = 0 (4) The condition ΔP_rec(t ≤ 0) = 0 is a model assumption: daylight is taken to hold the cells in the recovered state. The loss in operation that a warranty claim compares with nameplate and with the warranted minimum power in the module's warranty is therefore ΔP_perm, not ΔP(T) at the flight time T. In the lab example above it is at most 37 W (−5.9%, measured 1 h after recovery) against 77 W (−12.2%) after dark storage[1]. In TOPCon, UVID has been attributed to hydrogen redistribution in the SiNx/poly-Si stack, which raises a J01-dominated recombination current; the increase is metastable and partially recovered under illumination[2]. In the lab, dark-storage loss after light recovery reached about 1% of Pmax after 1 h and 2.5% after 6 h, at a module-dependent rate[1], and up to 1% per day has been reported for UVID-sensitive TOPCon[5]. On this basis the draft IEC TS 63624-⁠1 procedure, light soaking followed by I-⁠V within 4 h, may be too loose to give a field-representative Pmp[1].

Why · In the field

Night EL sees both losses. Time after sunset separates them.

Night EL is where UVID shows most clearly: in the dark, affected cells stand out from healthy ones. On this project, they kept getting darker after sunset and through the night as the recoverable loss built up[1], while healthy cells barely changed. Because every image carries its time after sunset, the two losses can be separated, and a claim can rest on the loss in operation.Night EL is the most sensitive view of UVID: it records the permanent and the recoverable loss together. Field data from this project show UVID-affected cells darkening after sunset and through the night, consistent with the recoverable loss building up[1], while healthy cells change little. With each image's time after sunset known, the recoverable part can be removed and the loss in operation reported.

Same module, two flights5 A

Night EL image of the module, 160 minutes after sunset at 5 A
Dusk EL image of the same module, 16 minutes after sunset at 5 A
Dusk EL · 16 min after sunset Night EL · 160 min after sunset
  • 0.97

    healthy cells, night brightness compared with dusk; no larger than the normal difference between two flightshealthy cells, EL ratio night ÷ dusk; within flight-to-flight noise

    dusk night
  • −0.20

    dark cells that recover, drop in brightness from dusk to night, as a share of the module's healthy level (about one fifth, give or take 0.05)recovering dark cells, change in r_i from dusk to night, in units of EL_ref, ± 0.05

    dusk night

Field data, this project: the same 20 strings flown 7 to 17 min after sunset and again 2.5 to 2.7 h after sunset; 580 modules compared cell by cell at the same current, 5 A. Brightness is measured against each module's healthy level, the brightness of its own healthy cells. Healthy cells hardly changed. Most dark cells were about one fifth of the healthy level brighter at dusk than at night. The darkest cells changed less, and many cells only just below the dark-cell threshold did not change at all: they are naturally gray cells that never darkened.

Field data, this project: the same 20 strings flown 7 to 17 min after sunset and again 2.5 to 2.7 h after sunset; 580 modules compared cell by cell at 5 A. Levels are relative to each module's healthy level, EL_ref. The −0.20 applies to dark cells that recover; the darkest cells recover less, and many cells near the dark threshold are naturally gray and do not recover.

Technical note Field data, this project. Repeat flights imaged the same 20 strings (580 modules) at 5 A, 7 to 17 min after sunset and again 2.5 to 2.7 h after sunset, and the two images were compared cell by cell; the module shown was imaged at 18:00 and 20:24, t = 0.27 h and 2.67 h after a 17:44 sunset. Healthy cells changed by no more than the flight-to-flight noise: EL_healthy(night) / EL_healthy(dusk) = 0.97 We therefore assume that healthy cells, and with them EL_ref, are stable over the night. Dark cells that recover lost a similar amount over a wide range of dusk levels: r_i(dusk) − r_i(night) = 0.20 ± 0.05 (recovering dark cells) A similar difference across levels points to an additive rather than a multiplicative change, which motivates the lift of Eq. (3). The change is not the same for every dark cell. The darkest cells recover less: 0.14 below a night level of 0.10 and 0.16 at 0.10 to 0.15, against 0.21 from 0.20 up. Near the dark threshold, the night level is a mixture: the share of cells that recover falls from about 99% at night levels of 0.15 to 0.35, to 69% at 0.45 to 0.50 and 26% at 0.60 to 0.65, because many of these cells are naturally gray and never darkened. About 5% of the dark cells do not recover at all (117 cells on 33 modules: permanently inactive cells and a darker band along the frame, likely edge soiling). The correction therefore tapers the lift near the threshold and reduces it for the darkest cells (Step 4). Localized dark regions within otherwise healthy cells also darken. For a claim, the consequence is that power inferred from a night image includes ΔP_rec(T), Eq. (4), and so depends on when the module was flown.

Modules with very dark cells · below-15% classdarkest classsame images, same thresholds

Whole project

Night EL measured2,396
Corrected to daylight modeled12

Dusk check · 580 modules

Night EL measured101
Dusk flight measured5
Corrected modeled0

Counted on the night images, very dark cells appear on 2,396 modules. Corrected to daylight, they remain on 12. The dusk flight confirms this: on the 580 modules flown again at dusk, 101 modules showed very dark cells at night, only 5 at dusk and none after correction.Very dark cells appear on 2,396 modules at night but on 12 after correction; the dusk flight confirms the drop (101 modules at night, 5 at dusk, 0 corrected, on the same 580 modules).

Field data, this project. Night and dusk counts are measured; the corrected counts are modeled. The very dark cells that remain in daylight are permanently inactive cells, not the recoverable loss.

Field data, this project. Counts on cell levels with the same thresholds for all images; night and dusk counts measured, corrected counts modeled. Very dark cells that remain in daylight are permanently inactive cells.

  • Captures both losses
  • Every image timed after sunset
  • Loss in operation, separated

A claim needs the loss in daylight operation, so the night image needs correcting.A claim needs the loss in operation, so the night image must be corrected.

How

Six steps from a night flight to power loss per module.

How · Steps 1 and 2

Fly through the night. Measure each module against itself.

The correction starts with how the plant is flown. The drone flies from dusk into the night and images each module once, so different modules are imaged at different times after sunset. Together, they show how dark cells change through the night. Each cell is measured against its own module's healthy cells, so one image per module is enough. Only a small sample, 20 strings, is flown a second time, just after sunset, to pin down the start of the curve.Modules imaged at different times after sunset sample the darkening curve cross-sectionally. Each cell is normalized to its own module's healthy level, so the survey images each module once; a sample of 20 strings is also flown just after sunset to calibrate the early part of the curve.

Step 1 · Fly from dusk into the night

9,353 modules
Field data, this project · modules flown in each 15 minutes after local sunset · 9,353 night modules over four nights, flown 0.3 to 5.8 h after sunset · bar heights show the approximate spread.Field data, this project · modules per 15-min bin of t, the time after local sunset · 9,353 night modules over four nights, t = 0.3 to 5.8 h · bar heights approximate.

Step 2 · Compare each cell with its module and find dark cellsNormalize and find dark cells

2.67 h after sunset
Example module, night EL, 2.67 h after sunset · illustrative: each cell's brightness is read from the image and divided by the module's healthy level, the brightness of its healthy cells. Cells below 0.6 of that level count as dark.Example module, night EL, T = 2.67 h · illustrative: r_i read from image pixels, Eq. (1); dark-cell threshold r_i < 0.6.
Technical note Each cell i is normalized to its module's healthy level: r_i = EL_i / EL_ref, EL_ref = P90 of the module's cells (1) To first order this removes differences in camera, exposure, flight conditions and module brightness. It assumes that the P90 cells are unaffected by UVID, so that at least the brightest tenth of each module's cells is healthy, and that healthy cells are stable over the night, which the paired flights support: all cells agree between night and dusk within a bias of −1.0% and a flight-to-flight repeatability of 1.7% of the healthy level (field data, this project). A cell is classed as dark if r_i < 0.6; the threshold is a choice, and its effect is discussed under Limitations. The time after sunset t of each module is computed from its GPS position and image timestamp. Each of the 9,353 night modules (four nights, t = 0.3 to 5.8 h) was imaged once, so the data set is cross-sectional and samples r(t) at different t: an early group up to about 0.5 h and the main survey from about 1.5 h. Every part of the array was flown within a few minutes, so time after sunset and module population are mixed in this data set. A paired sample therefore calibrates the early part of the curve: the same 20 strings (580 modules) flown 7 to 17 min after sunset and again 2.5 to 2.7 h after sunset (Step 3).

How · Step 3

One curve through thousands of dark cells.

Next, the dark cells are grouped by flight time, in steps of 15 minutes after sunset. The typical dark cell in each group gives one point. One smooth curve through these points is the project's darkening curve. Its darkening time constant, τ, sets how fast dark cells darken: the shorter τ, the faster.The median dark cell in each 15-minute bin of t, fitted with one empirical exponential for this project. Its time constant τ sets the speed of darkening.

Step 3 · Bin, take the median, fit τGroup, take the typical cell, fit τ

τ is fitted per project

  • Dark cells
  • Bin median · size = cell countTypical dark cell per 15 min · size = number of cells

Points are illustrative. The curve is fitted to field data, this project: 9,353 night modules over four nights, flown 0.3 to 5.8 h after sunset, and the same 20 strings (580 modules) flown at dusk and at night. A typical dark cell sits at 0.53 of the healthy level at sunset and falls toward 0.25 during the survey hours, with τ of 0.84 h. These values apply to this project only, and dark cells keep darkening through the night. An earlier curve fitted to the night flights alone left corrected cells 10% too dark, because the night flights cannot show how far the cells fell in the first hour after sunset. That is why a few strings are also flown at dusk. An earlier fit on night data alone under-corrected, leaving cells 10% too dark; paired dusk strings fix the sunset level.

Technical note The typical dark cell, in units of its module's healthy level, is described by an empirical exponential in t: r(t) = r_∞ + (r_sun − r_∞)·exp(−t/τ), t ≥ 0 (2)r(t) = r_sun, t < 0 (daylight) Dark cells (r_i < 0.6) from all night modules are grouped into 15-min bins of t, each bin b is represented by the median m_b of its n_b cells, and bins with n_b < 20 are excluded. τ is scanned from 0.1 to 6 h; at each τ, Eq. (2) is linear in r_∞ and r_sun, which are solved by linear least squares on the bin medians with weights √n_b, and the τ with the smallest weighted residual is retained. The night flights (9,353 modules over four nights, t = 0.3 to 5.8 h) pin r_∞; their within-array trend after 1.5 h, about −0.004 per hour, agrees with the curve. Because every part of the array was flown within a few minutes, time and module population are mixed, so the drop from sunset to night is pinned by paired flights of the same 20 strings (580 modules) at 7 to 17 min and 2.5 to 2.7 h after sunset, in which recovering dark cells differ by 0.20 ± 0.05 of EL_ref. Field data, this project: r_sun = 0.529, r_∞ = 0.25, τ = 0.84 h; these values apply to this project only, and parameter uncertainties are not reported here. An earlier fit on the night data alone (r_sun 0.436, r_∞ 0.314, τ 0.72 h) lifted dark cells by only 0.09 and left the corrected cells 10% too dark against the dusk flight, which is why paired dusk strings are flown. r_∞ is the level approached within the survey window, not an end point: cells keep darkening through the night, and behavior beyond about 6 h after sunset is not covered by these data. Identifying all three parameters requires data within about 1 h of sunset and beyond about 2 h; a survey that starts late constrains only r_∞.

How · Step 4

Lift each dark cell by the curve amount, weighted by its night level.

The darkening curve sets how far to brighten the dark cells, as a share of the module's healthy level. Healthy cells are left as they are. A clearly dark cell gets the full amount read from the curve. Gray cells, between 0.35 and 0.75 of the healthy level at night, get less the lighter they are, because many of them are naturally gray and never darkened. The very darkest cells also get less, because they recover less. Cracked cells and cells that received no current are kept as measured.Healthy cells are unchanged. Each dark cell is lifted by the curve amount r(t′) − r(T), in units of its module's healthy level EL_ref: in full for clearly dark cells, tapered between night levels 0.35 and 0.75, and reduced for the darkest cells. Cracked cells and cells without current injection keep their measured level.

Step 4 · Lift dark cells along the curve

EL level · fraction of the healthy levelBrightness · share of the module's healthy level

  • Night EL · 160 min after sunset (measured level)
  • Lifted to 16 min after sunset (modeled)
  • Lift · full 0.20, tapered or reducedLift · full 0.20, less for gray and darkest cells

Field data, this project: on the same 20 strings (580 modules) flown at night and again at dusk, recovering dark cells regained 0.20 ± 0.05 of the healthy level. The share of cells that recover falls from about 99% at night levels of 0.15 to 0.35 to 69% at 0.45 to 0.50 and 26% at 0.60 to 0.65, and the darkest cells regained only 0.14 to 0.16. Example cells are illustrative, with a full lift of 0.20.

Field data, this project: the same 20 strings (580 modules) were flown at night and again at dusk. Dark cells that recovered were 0.20 of the healthy level brighter at dusk, give or take 0.05. Almost all cells at night levels of 0.15 to 0.35 recovered, but only 69% at 0.45 to 0.50 and 26% at 0.60 to 0.65, and the darkest cells recovered only 0.14 to 0.16. So each dark cell gets an amount, not a multiple, weighted by how dark it was at night. Example cells are illustrative, with a full lift of 0.20.

Technical note A cell i imaged at time T after sunset is mapped to a target time t′ by a weighted additive lift along the project curve, Eq. (2): r_i(t′) = r_i(T) + w_taper(r_i)·w_depth(r_i)·[r(t′) − r(T)] (3)w_taper = 1 for r_i ≤ 0.35, 0 for r_i ≥ 0.75, linear between; w_depth = 0.62 for r_i ≤ 0.10, linear to 1 at r_i ≥ 0.20 Both bands are given at T = 2.6 h and move with the curve for other flight times, band(T) = band(2.6 h) + r(T) − r(2.6 h): a night level is only meaningful together with the time the module had been in the dark. Cracked cells and cells of half-strings without current injection keep their measured level, since their darkness is not dark-storage loss. The rule rests on the paired flights (field data, this project; 20 strings, 580 modules, 7 to 17 min and 2.5 to 2.7 h after sunset). Recovering dark cells regained 0.20 ± 0.05 of EL_ref, as an amount rather than a ratio. The night level is a mixture: the share of cells that recover falls from about 99% at 0.15 to 0.35 to 69% at 0.45 to 0.50 and 26% at 0.60 to 0.65, above which most cells are naturally gray and never darkened, hence the taper. The darkest cells recover less, 0.14 below 0.10 and 0.16 at 0.10 to 0.15, against 0.21 from 0.20 upwards, hence the depth factor. A single shift for every dark cell over-corrects gray cells and the darkest cells. For the two flight times of the example module the curve gives r(0.27 h) − r(2.67 h) ≈ 0.19; the illustrative cells above use a full lift of 0.20, giving lifts of about 0.825 × 0.20 at 0.42 and 0.73 × 0.20 at 0.13.

How · Step 5

Correct every night image to the daylight state.

Applied to every dark cell with the rule of Step 4, the lift moves the whole night image back along the darkening curve to sunset. That is the daylight state, the state a module is in after time in the light. The corrected image, called daylight-equivalent EL, removes the recoverable loss that built up in the dark and keeps the permanent loss. Step 6 turns it into module power. On this project, a typical dark cell sits at 0.53 of its module's healthy level at sunset and falls toward 0.25 during the night survey. Moving the image to the time of the dusk flight, instead of to sunset, allows a direct check against the dusk image.Each night image is lifted with Eq. (3) along this project's curve to t′ = 0, the light-recovered state at sunset. The result, daylight-equivalent EL, removes the recoverable night loss and keeps the permanent loss; it is the input to the power calculation in Step 6. A typical dark cell sits at r_sun = 0.53 of its module's healthy level at sunset and falls toward r_∞ = 0.25 during the night survey; other target times serve the dusk-flight check.

  • τ 0.84hDarkening time constant · this projectTime constant τ · this project
  • 0.53At sunset · daylight stater_sun · at sunset
  • 0.25Night level · during the surveyr_∞ · night level
Typical dark cell level against hours from sunset, minus 1 to 6 h: flat at 0.53 in daylight up to sunset, then falling with tau 0.84 h toward a night level of 0.25. Measured flights at 0.27 h (dusk) and 2.67 h (night). The selected time is marked on the curve; drag to change it.
Measured night EL of the module, 160 minutes after sunset, 5 A Daylight-equivalent EL of the module (modeled), lifted from the night image to sunset Measured dusk EL of the same module, 16 minutes after sunset, 5 A
17:44 sunset Modeled from night EL

Curve fitted on field data, this project. Measured: the night image, 2.67 h (160 min) after sunset, and the dusk image, 0.27 h (16 min) after sunset, both at 5 A. Modeled: every other time, moved from the night image along the curve with the lift rule of Step 4. Moved to the dusk flight's own time, the corrected dark cells agree with the dusk images of 580 modules without bias, within about 6% of the healthy level per cell.Curve: Eq. (2), fitted on field data, this project. Measured: night EL at T = 2.67 h and dusk EL at 0.27 h after sunset, both at 5 A. Modeled: every other time, lifted from the night image with Eq. (3). Simulated to the dusk flight time, dark cells on 580 paired modules show bias +0.1% and RMS 5.7% of the bright level.

Technical note Daylight-equivalent EL applies Eq. (3) with t′ = 0, where r(0) = r_sun = 0.529, the modeled light-recovered state at sunset: r_i(0) = r_i(T) + w_taper(r_i)·w_depth(r_i)·[r_sun − r(T)] The lift removes the recoverable part and keeps the permanent part: a cell that is dark at sunset stays dark in the daylight-equivalent image. In Step 6, power calculated from the lifted image gives ΔP_perm of Eq. (4), the loss in operation on which a claim rests, and its difference from the power calculated on the night image gives ΔP_rec(T). The lift is applied per pixel within each cell, so the pattern inside the cell is kept; healthy cells are unchanged, gray cells get a tapered lift and the darkest cells a reduced one. Cracked cells and cells without current injection keep their measured level, since they are dark for reasons other than UVID. The curve describes the typical dark cell of this project, with τ = 0.84 h fitted on this project only. Individual cells deviate from it: recovering cells regain 0.20 ± 0.05 of EL_ref, and about 5% of the dark cells on the paired modules did not recover in daylight. Per cell, the corrected level is unbiased on average and within about 6% of the bright level (RMS 5.7% on 2,328 dark cells, 580 modules, simulated to the dusk flight time).

How · Step 6

From corrected EL to module power.

Per-cell severity from the corrected EL image feeds a circuit model of the module, giving Pmax at STC[2]. Taken in the daylight state, it estimates the module's power in operation, to compare with the warranted minimum power.

The last step turns the corrected image into watts. The image shows how strongly each cell is affected. A circuit model of the module combines the cells into the module's maximum power under standard test conditions[2]. Because the image is in the daylight state, the result estimates the module's power in operation, the value to compare with the warranted minimum power.

Step 6 · EL to module power, one lab module[1]

Shown: 1 h after light soaking · light-recovered, daylight state

  1. a · EL image

    Lab EL of the module after dark storage: cells are dim Lab EL of the module 1 h after light soaking: cells are bright Lab EL of the module 4 h back in the dark: cells are dimmer again
    Measured · 1 h after light

    Field: night EL corrected to the daylight state, t′ = 0, Eq. (3).

    In the field: the night image, corrected to the daylight state in Step 5.

  2. b · Per-cell severityb · How affected each cell is

    Degradation mode: J01-dominated recombination[2].

    Each cell is scored assuming UVID acts through one type of damage: extra charge losses inside the cell[2].

  3. c · Module Pmax at STCc · Module maximum power

    593W−5.9% vs 630 W

    Cells in a module circuit model at 1 Sun[2]. Value shown: flash I-⁠V[1].

    The cells are combined in a circuit model of the module under full sunlight[2]. Value shown: measured with a lab flash tester[1].

Lab data[1], one 630 W TOPCon module, EL at 1 A; Pmax from flash I-⁠V. The dark-storage image stands in for an uncorrected night image, the light-recovered image for the corrected daylight state. Severity shading and I-⁠V curve are illustrative, not model output.

Lab data[1], one 630 W TOPCon module, EL at 1 A; power measured with a lab flash tester. The image after dark storage stands in for an uncorrected night image, and the image after light recovery for the corrected daylight state. The cell shading and the power curve are illustrative, not model output.

Same module, three states[1]

Pmax at STC · WMaximum power at standard test conditions · W

  • Loss in operation · permanent
  • Implied by an uncorrected night stateWhat the raw night image would suggest

Claim basis: at most ≈37 W lost in operation, not ≈77 W.Claim basis: at most about 37 W lost in operation, not about 77 W.

Lab data[1], one module; Pmax at STC from flash I-⁠V. The 593 W reading was taken 1 h after recovery, with the module already back in the dark, so the loss in operation is at most about 37 W. The 40 W between 593 W and 553 W is recoverable in light.

Lab data[1], one module, measured with a lab flash tester. The 593 W reading (−5.9%) was taken 1 h after light exposure, with the module already back in the dark, so the loss in operation is at most about 37 W. The other 40 W, down to 553 W (−12.2%), is recoverable loss.

EL-to-power vs flash I-⁠VHow accurate is power from EL?[2]

20 TOPCon modules · one 6 A EL image each, about 40% of Isc

20 TOPCon modules · power from one EL image each, against the lab flash test · about 1% typical error

  • Verification setModules used to check the model
  • Calibration setModules used to tune the model
  • 1:1 · ±1.1%Perfect match · ±1.1% band
0.910Pmax R²Power · R² (1 is a perfect match)
1.1%Pmax RMSEPower · typical error
0.929Voc R²Voltage · R²
0.6%Voc RMSEVoltage · typical error

Re-plotted from [2], Fig. 5. Statistics for the verification set[2].

Re-plotted from [2]. Each point is one module; the closer it sits to the dashed line, the closer power from EL is to the lab measurement. On the modules used to check the model, the typical error is about 1% (1.1%, about 6.5 W on a 593 W module)[2].

Technical note Step 6 applies the degradation-mode EL-to-power method of [2]. Each cell's EL, taken at 6 A (about 40% of Isc), is converted to a severity under the assumption that UVID acts through a J01-dominated increase in recombination (one linear degradation mode); the cells are then placed in a circuit model of the module and simulated at 1 Sun to give Pmax and Voc at STC. The conversion runs on the night image (time T) and on the image corrected to the daylight state (t′ = 0, Eq. (3)), which splits the loss as in Eq. (4): ΔP_perm = ΔP(0) (loss in operation, daylight state)ΔP_rec(T) = ΔP(T) − ΔP_perm (recoverable, present at flight time T) The model is calibrated per module type against lab flash I-⁠V, and a sample of field modules is flash-tested to benchmark each project. On 20 TOPCon modules [2], Pmax R² 0.910 and RMSE 1.1% (about 6.5 W at 593 W), Voc R² 0.929 and RMSE 0.6%. Limits: the linear single-mode assumption does not cover every defect type; Pmax is over-predicted for some of the deepest dark-storage states (scatter above), so ΔP(T) can be underestimated; EL and I-⁠V depend on temperature and must be referred to a common temperature. The model is calibrated at a given drive current (6 A in [2]); field images taken at another current, such as the 5 A flights of this project, need a calibration at that current before the conversion. [2] is in revision; its figures may change.

Result

A claim-ready power loss, checked in the field and in the lab.

Result · Claim-ready report

Power loss in operation, module by module.

For each module, the report gives its power in daylight operation, with permanent and recoverable loss shown separately, ready to set against the warranted minimum power in its module warranty.All six steps lead to one report. For each module, it gives the power in operation, with the permanent and recoverable loss shown separately, ready to compare with the warranted minimum power in the module warranty.

One string · power in operation vs warranted minimum

Module Pmax · illustrative scaleModule power · illustrative scale

Illustrative
  • Warranted minimum power (illustrative; per the module warranty)
  • Raw night EL at survey time
  • In operation · corrected to t′ = 0In operation · corrected to the daylight state
  • Claim candidate · below the line in operation
  • Selected module · ±1.1% Pmax RMSESelected module · typical error about 1%[2]

Illustrative values, not project results. The vertical gap is the recoverable loss at survey time.Illustrative values, not project results. The vertical gap is the recoverable loss at survey time. Judged on the raw night image, more modules fall below the line than in operation.

Module report card

Illustrative

584W

Power in operation · daylight state, t′ = 0corrected to the daylight state · −7.3% vs nameplate

Loss vs nameplatein operation
Nameplate
630 W
Permanent loss
46 W7.3%
Recoverable loss at survey time
38 W6.0%
Raw night state
546 W−13.3%
Survey time
2.4 h after sunset
Project τDarkening time constant, τ · this project
0.84 hfitted, dusk checkchecked at dusk
Corrected dark-cell levelAccuracy of the corrected image
±6%about 6%per cell, unbiasedper cell, no bias
Pmax uncertaintyTypical error of power from EL
±1.1%about 1%RMSEvs lab power tests[2]

Below the warranted minimum in operationClaim candidate

Report · what each project report includes

  1. 01Power in operation, per modulePmax at the light-recovered state, t′ = 0, from EL with the degradation-mode methodModule power corrected to the daylight state, calculated from EL with a published EL-to-power method[2].
  2. 02Permanent and recoverable splitΔP_perm and ΔP_rec at survey time, Eq. (4).The permanent loss, and the recoverable loss present at the time of the night flight.
  3. 03Project curve and accuracyData set, fit of r(t) and τ, and the dusk-flight check with its per-cell accuracy: on this project unbiased, about 6% of the bright level per cell, 580 modules.The night data behind the project darkening curve, its τ, and the dusk-flight check with its accuracy: on this project no bias on average, and about 6% of the healthy level per cell, checked on 580 modules.
  4. 04EL imagesNight EL and EL corrected to daylight, for each module.
  5. 05Lab EL and I-⁠V benchmarkLab EL and power benchmarkLab EL of a sample of modules in the light-recovered state, compared cell by cell with the corrected field images; Lab EL of a sample of modules in the daylight state, compared cell by cell with the corrected field images; flash I-⁠V compared with EL-derived power.power measured in the lab compared with power calculated from EL.
  6. 06Method referencesDark-storage study[1] and EL-to-power method[2].

Only UVID dark cells are treated here; other defects are assessed under the material warranty. Warranty terms and claim procedures differ by manufacturer and contract, so the report supplies technical evidence and does not decide the claim outcome.

Technical note The power in operation is the Pmax calculated with the degradation-mode method[2] from the EL image corrected to t′ = 0 with Eq. (3), the light-recovered state in which the module operates in daylight. With losses taken from nameplate, Eq. (4) splits the loss seen at survey time T: ΔP(T) = ΔP_perm + ΔP_rec(T), ΔP_rec(0) = 0 ⇒ P_op = P_nameplate − ΔP_perm The comparison with the warranted minimum power therefore uses the operating state, not the raw night state. Each step is traceable: per-module normalization, Eq. (1); a project curve r(t), Eq. (2), with τ fitted on the project's own night data and checked against a dusk flight of the same modules; the lift rule, Eq. (3), tapered by night level and reduced for the darkest cells; and a published EL-to-power method with a stated uncertainty, Pmax RMSE of about 1.1% on the verification set of 20 TOPCon modules imaged at 6 A[2]. The correction is validated against lab EL of a sample of the same modules in the light-recovered state, and EL-derived power is benchmarked to flash I-⁠V on that sample, and the dark-storage behavior being corrected is documented in the lab[1]. Field figures also carry the uncertainty of the correction, which the dusk check measures: on this project, the night images of 580 paired modules simulated to the dusk flight time were unbiased on average and within about 6% of the bright level per dark cell (bias +0.1%, RMS 5.7%), against −19.0% for the night EL as measured. Benchmark modules are flash tested in the light-recovered state soon after light soaking, since dark-storage loss starts as soon as they are back in the dark[1]. A module close to the warranted minimum should be judged with the stated Pmax uncertainty and the measurement tolerance in the warranty terms in mind. Only UVID dark cells are treated here; other defects are assessed under the material warranty. Warranty terms and claim procedures differ by manufacturer and contract, so the report supplies technical evidence and does not determine the claim outcome.

Result · Validation

Each project's curve, checked against a dusk flight.

The correction is checked in two ways. In the field, the same 20 strings are flown at night and again just after sunset. Each night image is moved back along the darkening curve to the time of the dusk flight and compared, cell by cell, with the dusk image of the same module. On 580 modules, the corrected image shows no bias and agrees within about 6% of the healthy level per cell. In the lab, EL images taken hours into the dark are corrected back to the daylight state[1]. Correcting a field image to the daylight state is the same step, taken all the way back to sunset.Field: 20 strings (580 modules) flown at night and again at dusk; each night image is shifted with Eq. (3) to the dusk flight's own time and compared cell by cell with the measured dusk image. Lab: EL images back-calculated to the light-recovered state[1]. Daylight-equivalent EL is the same step with t′ = 0.

Accuracy against a dusk flight · 580 modules

Checked against a real dusk flight, the corrected image is unbiased and within about 6% per cell.

Simulated to the dusk flight's time, dark cells show a bias of +0.1% and an RMS error of 5.7% of the bright level, against −19.0% for the night EL as measured.

1How far dark cells are from the dusk imageBias against the dusk EL, % of bright level

2Modules with very dark cells, of 580Modules with 15% class cells, of 580

3Where the remaining spread comes fromError budget of the 5.7% scatter

  1. 1.7%repeatability

    Two flights, same healthy cells. The same bright cells differ by this much between the dusk and the night flight (camera, exposure, alignment).Flight to flight. Same bright cells, two flights: camera, exposure and alignment.

  2. ≈5%of dark cells

    Cells that do not recover. They are as dark at dusk as at night: permanently inactive cells and likely soiling along the module frame. There are 117 such cells on 33 modules, and the correction lifts them anyway. Without them, the spread falls from 5.7% to 4.4%.Non-recovering cells (117 cells on 33 modules): permanently inactive cells and likely edge soiling, lifted anyway. Without them: bias −0.7%, scatter 4.4%.

  3. 0.20 ± 0.05of bright level

    Recovery differs cell by cell. Recovering dark cells regain 0.20 of the healthy level, give or take 0.05, varying from module to module (5.6%) and within a module (3.5%).Individual recovery. Spread between modules 5.6%, within a module 3.5%. Not reducible from a night image.

Field data, this project: the same 20 strings (580 modules) flown at night, 2.5 to 2.7 h after sunset, and again 7 to 17 min after sunset. Each night image is corrected to the dusk flight's own time (modeled) and compared cell by cell with the dusk image (measured). Percent of the module's healthy (bright) level. Limits: one array and one night, with one dusk pass; how the correction treats gray and very dark cells was tuned on these same cells.Field data, this project: 20 strings, 580 modules; night EL 2.5 to 2.7 h and dusk EL 7 to 17 min after sunset. Night EL simulated to each module's dusk recording time (modeled), compared cell by cell with the dusk EL (measured); dark-cell classes taken on the night EL. Bias and scatter in % of the module's bright (90th percentile) level. Limits: one array, one night, one dusk pass; the taper by night level and the reduced lift for the darkest cells were fitted on these cells.

In the field · One module, night scaled to dusk

Dark cell level against hours from sunset, minus 1 to 3 h: flat at 0.53 in daylight up to sunset, then falling. The night measurement at 2.67 h is scaled along the curve back to the dusk time of 0.27 h for validation, then on to sunset, which gives daylight-equivalent EL.
  1. Measured EL of the module, night flight 160 minutes after sunset, 5 A
    MeasuredNight EL · 160 min after sunset
  2. Night EL of the same module scaled to 16 minutes after sunset, modeled
    ModeledNight EL scaled to 16 min
  3. Measured EL of the same module, dusk flight 16 minutes after sunset, 5 A
    MeasuredDusk EL · 16 min after sunset

Example module, field data, this project: night image 160 min and dusk image 16 min after sunset, both at 5 A. For these two times the darkening curve predicts that a typical dark cell is 0.19 of the healthy level brighter at dusk. Across the 20 strings (580 modules) flown at both times, recovering dark cells were 0.20 brighter at dusk, give or take 0.05.

Example module, field data, this project: night EL at T = 2.67 h, dusk EL at 0.27 h, both at 5 A. Curve change between the two times 0.19 of the bright level (modeled); recovering dark cells on the 580 paired modules: 0.20 ± 0.05 (measured).

In the lab · power read from ELEL-derived Pmax[1],[2]

EL-derived maximum power of a UVID TOPCon module kept in the dark for 6 hours after light recovery. EL-derived values fall from about 597.5 W to about 582 W. The same images back-calculated to time zero stay flat at about 603 W.
Re-plotted from[1]: one UVID-affected TOPCon module, recovered with UV light and then kept in the dark for 6 h; power read from each EL image with the method of[2]. Power read from the raw images falls. The same images corrected back to the daylight state stay level, within about 2 W, because the correction removes the recoverable loss. Time here is hours in the dark in the lab, not time after sunset. Lab data, SERIS with Quantified Energy.Re-plotted from[1]: one UVID TOPCon module after UVA light recovery, 0 to 6 h in the dark; Pmax derived from each EL image with the method of[2]. Lab time is hours in the dark after recovery, not time after sunset. Lab data, SERIS with Quantified Energy.

Lab vs field · Darkening time constant

The lab curve has a fast part close to the field τ and a slow part that keeps darkening through the night.

In the lab, darkening has a fast part, about as quick as in the field, and a slow part that keeps darkening through the night.

Field · this projectτ 0.84 h
Lab · fast part[1]τ ≈ 1.3 h
Lab · slow part[1]τ ≈ 13 h

Longer bar, slower darkening. Field: τ fitted on this project's own night flights. Lab: QE analysis of one module from the dark-storage data set of[1], recovered with UV light and then kept 0 to 21 h in the dark. Its darkening is best described in two parts: a fast one, τ of about 1.3 h, close to the field value, and a slow one, about 13 h, that continues through the night. Fitted as a single part, the lab data give about 10 h, and that figure grows the longer the data run. During a night survey, the project curve mainly follows the fast part. Indicative: one module, from another site. Darkening speed depends on module type, history, temperature and light, which is why τ is measured on each project and checked with a dusk flight.

Longer bar, slower darkening. Field τ: Eq. (2), field data, this project. Lab τ: QE analysis of one module from the dark-storage data set of[1] (UVA recovery, 0 to 21 h in the dark, EL-derived Pmax), fitted with two exponential components. A single-component fit gives τ ≈ 10 h, and its value grows with the fit window. Indicative: one module, from another site.

Technical note Field check (field data, this project): the same 20 strings (580 modules) were flown at night, T = 2.5 to 2.7 h after sunset, and again 7 to 17 min after sunset. Both images of each module are reduced to their 144 cell averages and normalized to the module's bright (90th percentile) level; the night image is shifted along the project curve to the dusk image's own recording time and compared cell by cell. Cells the shift lifts (50% and 15% classes on the night EL, 2,328 cells): bias +0.1%, scatter 5.7%, RMS 5.7%, against −19.0% for the night EL as measured. 15% class alone (371 cells): bias 0.0%, RMS 5.8%, night as measured −15.1%. All 83,520 cells: bias −0.3%, RMS 2.2% (night as measured −1.0%). Shifted to t′ = 0, as in the report, the dark cells come out 5.3% brighter than the dusk EL: the darkening already present 7 to 17 min after sunset. Module counts with the same thresholds (night / dusk / simulated): 15% class 101 / 5 / 0; 50% class 223 / 179 / 169. Error budget: flight-to-flight repeatability 1.7% on the same bright cells; about 5% of the dark cells (117 cells on 33 modules) do not recover, being permanently inactive cells or likely soiling along the frame edge, and are lifted anyway (without them: bias −0.7%, scatter 4.4%); the rest is individual recovery, 0.20 ± 0.05 of the bright level (5.6% between module means, 3.5% within a module). Refitting the curve amplitude, a recovery table by night level and a classifier on 13 night-image features were tested and did not lower the RMS; the night level alone carries no information on whether a cell recovers. An earlier curve fitted on night data only lifted dark cells by 0.09 and left them about 10% too dark, which is why the paired dusk flight is part of the method. For the example module (T = 2.67 h, t′ = 0.27 h) the curve gives a change of 0.19 of the bright level. Limits: one array, one night, one dusk pass; the taper by night level and the reduced lift for the darkest cells were fitted on these cells (the latter cross-validated between odd and even strings, test RMS 0.4 to 0.5 points better); behavior beyond about 6 h after sunset is not covered. Lab check (QE analysis of the data set of[1]): Pmax derived from each EL image with the method of[2] falls during dark storage, whereas back-calculation of the same images to t = 0 agrees within ≈2 W for images taken up to 21 h in the dark. A single exponential fitted to the lab series gives τ ≈ 10 h, but the value grows with the fit window (about 3.5 h over 0 to 6 h, 7 to 10 h over 0 to 21 h), a sign of more than one component. Two components describe the series better (residual standard deviation 0.23 W against 0.59 W): a fast one with τ ≈ 1.3 ± 0.4 h, of the same order as the field τ of 0.84 h, and a slow one with τ ≈ 13 ± 3 h, consistent with darkening that continues through the night. This is QE analysis of one module, using EL-derived Pmax rather than the dark-cell level r, so it is indicative. Within a night survey window, Eq. (2) mainly captures the fast component. Kinetics are expected to depend on module type, history, temperature and light dose, which is why τ is fitted for each project and checked with a dusk flight.

Result · Evidence

The evidence behind each step.

Each part of the result is tested in the lab. Power from EL is checked against power measured in the lab. The need to correct night EL comes from lab power tests during dark storage. The correction itself is checked by taking lab images back to the daylight state, and in the field against a dusk flight of the same modules.Each part of the power-loss figure traces to lab measurement: the EL-to-power conversion against flash I-⁠V, the need to correct night EL from dark-storage I-⁠V checkpoints, and the correction itself from back-calculation of lab images and, in the field, from a cell-by-cell comparison with a dusk flight.

  • R squared 0.91:

    Step 6 · powerSingle EL image to module power, 20 TOPCon modules

    R² shows how closely power from EL matches power measured in the lab (1 is a perfect match); typical error about 1%, one EL image per modulePmax R² 0.910, RMSE 1.1%, verification set, one 6 A EL image per module · Re-plotted from [2]

    [2]IEEE JPV, in revision
  • 2.5 percent:

    Why correctPower lost within 6 h in the darkPmax lost within 6 h of dark storage

    Lab power tests on UVID-affected TOPCon modules kept in the dark after light recovery; about 1% after the first hour, at a rate that differs from module to moduleUVID TOPCon after light recovery, flash I-⁠V checkpoints; about 1% after 1 h, module dependent

    [1]EU PVSEC 2026
  • Within about 2 watts:

    Step 5 · correctionPower from EL taken in the dark, corrected back to the daylight stateEL-derived Pmax back-calculated to t = 0, the light-recovered state

    matches within about 2 W, for images taken up to 21 h in the darkagrees within ≈2 W for images taken up to 21 h in the dark

    QE analysis of the [1] dataset
  • Within about 6 percent per cell:

    Step 5 · field checkCorrected dark cells against a real dusk flight, 580 modulesSimulated dark-cell levels against a dusk flight, 580 modules

    No bias on average, and about 6% of the healthy level per cell; read directly from the night image, the same cells are 19% of the healthy level too darkbias +0.1%, RMS 5.7% of the bright level on 2,328 dark cells; night EL as measured −19.0%

    Field data, this project
Technical note The cards map to the claim workflow: card 1 supports the power calculation of Step 6, card 2 the reason night EL must be corrected, card 3 the correction of Step 5, and card 4 the field check of Steps 4 and 5 together. Card 1 is re-plotted from[2] Fig. 5: 20 TOPCon modules fielded for at least 6 months in a tropical climate were each measured after extended dark storage and after light soaking, and Pmax and Voc were inferred from a single 6 A EL image (about 40% of Isc) with the degradation-mode method. On the verification set (filled dots; open dots are the calibration set) this gave Pmax R² 0.910 with RMSE 1.1%, and Voc R² 0.929 with RMSE 0.6%. Card 2[1]: UVID-affected TOPCon modules were light recovered and then stored in the dark with flash I-⁠V checkpoints; Pmax fell by about 1% after 1 h and 2.5% after 6 h, at a module-dependent rate. Card 3 is a QE analysis of the data set of[1]: EL-derived Pmax back-calculated to t = 0 agrees within ≈2 W for images taken up to 21 h in the dark, while the uncorrected EL-derived Pmax falls. Card 4 is field data, this project: the same 20 strings (580 modules) were flown 2.5 to 2.7 h and 7 to 17 min after sunset, and each night image was simulated to the recording time of the dusk flight and compared cell by cell. On the 2,328 cells lifted (50% and 15% classes on the night EL), bias +0.1% and RMS 5.7% of the bright level, against −19.0% for the night EL as measured; on the 371 cells of the 15% class, bias 0.0% and RMS 5.8%. One array, one night and one dusk pass; the taper and depth factor of Eq. (3) were fitted on these cells. Quantitative EL power estimation itself was first published for PID-affected modules in 2018[3]. Status: reference [2] is in revision and reference [1] is a conference presentation, so these results are not yet fully peer reviewed.

Status: reference [2] is in revision and reference [1] is a conference presentation, so these results are not yet fully peer reviewed.

Quantified Energy is a spin-off of the Solar Energy Research Institute of Singapore (SERIS) at the National University of Singapore.

Technical · Methods and limitations

Data, model and limits.

The data sets, notation, the model behind Steps 1 to 6, fitted parameters, limitations, and the claim workflow on a new project. Field values come from one project and do not transfer to others.

Data · Field and lab data sets

Data setSize and conditionsUsed forLabel
Project field data set 9,353 night modules · four nights · flown 0.3 to 5.8 h after sunset · 5 A drive current · each module imaged once Fit of Eq. (2): pins r_∞; within-array trend after 1.5 h, about −0.004 per hour, consistent with the curve Field data, this project
Paired-flight subset 20 strings · 580 modules · one array · imaged 7 to 17 min after sunset and again 2.5 to 2.7 h after sunset, same night · 5 A Drop from sunset to night (pins r_sun): recovering dark cells regain 0.20 ± 0.05 of EL_ref; taper band and depth factor of Eq. (3); cell-by-cell accuracy check of the correction Field data, this project
Lab data [1] UVID TOPCon modules · light recovery, then dark storage · flash I-⁠V and EL checkpoints Dark-storage kinetics (≈1% Pmax loss after 1 h, 2.5% after 6 h, module dependent); QE analysis: EL-derived Pmax back-calculated to t = 0, lab refit of τ Lab data [1] · QE analysis
Lab data [2] 20 TOPCon modules · at least 6 months tropical field exposure · 6 A EL (≈40% of Isc) · dark storage and light soaking Step 6: EL-to-power conversion from a single EL image (degradation-mode analysis); verification set Pmax R² 0.910, RMSE 1.1%; Voc R² 0.929, RMSE 0.6% Lab data [2]

Nomenclature · Symbols used on this page

t
Time after local sunset at the module's position; t < 0 is daylight
h
T
Time after sunset at which a module was imaged
h
t′
Target time of the lift; t′ = 0 gives daylight-equivalent EL, the input to Step 6
h
EL_i
EL signal of cell i (or of a pixel within it) at fixed drive current
a.u.
EL_ref
Healthy level of the module: P90 of its cells' EL_i
a.u.
r_i
Normalized level of cell i, EL_i / EL_ref, Eq. (1); dark if r_i < 0.6
1
r(t)
Level of the typical (median) dark cell at time t, Eq. (2)
1
r_sun
r(t) for t ≤ 0: the light-recovered level at sunset
1
r_∞
Level approached within the survey window; not an end point
1
τ
Time constant of darkening after sunset; project-specific
h
w_taper, w_depth
Weights of the lift by night level r_i(T): taper for gray cells, depth factor for the darkest cells, Eq. (3)
1
n_b, m_b, t_b
Dark-cell count, median r_i and time of 15-min bin b
1, 1, h
ΔP, ΔP_perm, ΔP_rec
Pmax loss estimated from EL[2]; its permanent and recoverable parts, Eq. (4)
W or %

Model · Steps 1 to 6

  1. Fly and assign time. Modules are imaged at one drive current from dusk into the night. Each module carries its time after sunset t, computed from GPS position and image timestamp. Each module is imaged once, so the data set is cross-sectional.
  2. Normalize per module. Each cell's EL is divided by its module's healthy level, which cancels camera, exposure, flight conditions and module brightness to first order. Assumptions: the P90 cells are unaffected by UVID, and healthy cells are stable over the night (night/dusk 0.97, field data, this project). (1)r_i = EL_i / EL_ref, EL_ref = P90 of the module's cells; dark cell: r_i < 0.6
  3. Bin and fit. Dark cells are grouped in 15-min bins of t; bin b holds n_b dark cells with median m_b at time t_b, and bins with n_b < 20 are excluded. Eq. (2) is an empirical model, flat before sunset. τ is scanned from 0.1 to 6 h; at each τ the model is linear in r_∞ and r_sun, which are solved by weighted linear least squares, and the τ with the smallest objective is retained. The night flights pin r_∞; since every part of the array was flown within a few minutes, time and module population are mixed, so the drop from sunset to night is pinned by the paired flights. (2)r(t) = r_∞ + (r_sun − r_∞)·exp(−t/τ), t ≥ 0
    r(t) = r_sun, t < 0 (daylight)
    min over r_sun, r_∞, τ: Σ_b √n_b·[m_b − r(t_b)]²
  4. Lift rule. A cell imaged at T is moved to a target time t′ by the curve amount r(t′) − r(T) in units of EL_ref, applied per pixel within the cell and weighted by the cell's night level: in full for clearly dark cells, tapered for gray cells, reduced for the darkest cells. Healthy cells, cracked cells and cells without current injection keep their measured level. (3)r_i(t′) = r_i(T) + w_taper(r_i)·w_depth(r_i)·[r(t′) − r(T)] w_taper = 1 (r_i ≤ 0.35), 0 (r_i ≥ 0.75), linear between
    w_depth = 0.62 (r_i ≤ 0.10), 1 (r_i ≥ 0.20), linear between
    band(T) = band(2.6 h) + r(T) − r(2.6 h)
  5. Correct to daylight. Every night image is lifted with Eq. (3) to t′ = 0, the light-recovered state at sunset, giving daylight-equivalent EL. Lifting to the dusk flight time instead gives the field check.
  6. Calculate power. Pmax is calculated with the degradation-mode EL-to-power method[2] (20 TOPCon modules, one 6 A EL image each: Pmax R² 0.910, RMSE 1.1%) from the daylight-equivalent image, giving ΔP_perm, and from the night image, giving ΔP(T); their difference is ΔP_rec(T). EL-derived power is benchmarked to flash I-⁠V on a sample of modules. ΔP_rec(t ≤ 0) = 0 is a model assumption. (4)ΔP(t) = ΔP_perm + ΔP_rec(t), ΔP_rec(t ≤ 0) = 0

Parameters · This project

r_sun0.529Dark-cell level at sunset, the light-recovered state; r(t) for t ≤ 0
r_∞0.25Level approached within the survey window; cells keep darkening through the night, so this is not an end point
τ0.84 hTime constant of darkening after sunset; specific to this project
taper0.35 / 0.75Night levels at which the lift starts to fall below full and reaches zero; given at T = 2.6 h, moved with the curve for other T
w_depth0.62Lift factor at r_i ≤ 0.10, rising linearly to 1 at r_i = 0.20; given at T = 2.6 h

Field data, this project: 9,353 night modules over four nights, and 20 paired strings (580 modules) flown at dusk and at night. Levels in units of EL_ref. The taper band and the depth factor were fitted on the paired cells; the depth factor was cross-validated between odd and even strings (test RMS 0.4 to 0.5 points better). An earlier curve fitted on night data alone (r_sun 0.436, r_∞ 0.314, τ 0.72 h) lifted dark cells by only 0.09 and left them about 10% too dark. Parameter uncertainties and goodness-of-fit statistics are not reported here. If a later survey on this project starts late, its data constrain only r_∞, and r_sun and τ from this fit can serve as priors; they should not be transferred to other projects.

Sensitivity to τ

Illustrative
Illustrative: Eq. (2) with r_sun = 0.529, r_∞ = 0.25 and τ = 0.5, 0.84 and 2 h. The curves differ most within the first hour after sunset, so data from that window are needed to identify τ.

Accuracy · Field check of the correction

On the 580 paired modules, both images are reduced to their 144 cell averages and normalized to the module's EL_ref. Each night image is lifted with Eq. (3) to the dusk flight's own recording time and compared cell by cell with the dusk image. Cells are classed on the night EL. Values in % of EL_ref; field data, this project.

Cells (night EL class)CellsBias, correctedScatter / RMS, correctedBias, night EL as measured
Dark, 50% and 15% classes2,328+0.1%5.7% / 5.7%−19.0%
15% class only3710.0%5.8% / 5.8%−15.1%
All cells83,520−0.3%2.2% / 2.2%−1.0%
  • Module counts. With the same thresholds on the three images (night EL / dusk EL / corrected to dusk time): modules with 15% class cells 101 / 5 / 0; with 50% class cells 223 / 179 / 169.
  • To sunset. Lifted to t′ = 0, as in the report, the dark cells come out 5.3% brighter than the dusk EL: the darkening already present 7 to 17 min after sunset.
  • Statement for reports. Dark-cell levels within about 6% of EL_ref per cell, unbiased on average; 15% class cells that remain in the daylight-equivalent image are permanently inactive cells.
  • Error budget of the 5.7% scatter. Flight-to-flight repeatability on the same bright cells: 1.7%. Cells that do not recover: about 5% of the dark cells (117 cells on 33 modules), permanently inactive cells and likely soiling along the frame edge, lifted anyway; without them bias −0.7%, scatter 4.4%. The rest is individual recovery, 0.20 ± 0.05 of EL_ref (5.6% between module means, 3.5% within a module).
  • Floor of a night image. Refitting the curve amplitude (RMS 6.4% to 6.1%), a recovery table by night level (6.2%) and a classifier on 13 night-image features did not lower the RMS; the night level alone carries no information on whether a cell recovers. With the taper and depth factor, the model is at the floor set by individual recovery, repeatability and non-recovering cells.

Limitations

  • Typical cell, not each cell. Eq. (2) describes the median dark cell of the project. Individual recovery varies, 0.20 ± 0.05 of EL_ref, which sets most of the per-cell scatter of about 6% of EL_ref; it cannot be predicted from a night image alone.
  • Area and time. In cross-sectional data, time after sunset is linked to which part of the plant was imaged, and a cell is classed as dark at the time it was imaged, so bins at different t contain different populations. On this project a curve fitted on night data alone lifted dark cells by only 0.09; paired flights of the same strings at dusk and at night are needed to pin the drop.
  • Fitted on the checked cells. The accuracy comes from one array, one night and one dusk pass. The taper band and depth factor were fitted on the same paired cells; only the depth factor was cross-validated, between odd and even strings.
  • Reference level. EL_ref assumes that the P90 cells are unaffected by UVID and stable over the night. In modules where most cells are affected, EL_ref would be low and r_i biased upwards.
  • Cells not lifted, cells that do not recover. Cracked cells and cells without current injection keep their measured level. About 5% of the dark cells on the paired modules did not recover in daylight (permanently inactive cells, likely soiling at the frame edge) and are lifted anyway, which makes the daylight-equivalent image slightly optimistic for them.
  • Conditions. Module temperature can differ between dusk and night flights and may contribute to the observed change. Module technology, history and site conditions affect τ.
  • Daylight state. t′ = 0 is taken as the light-recovered state of operation, ΔP_rec(t ≤ 0) = 0. r_sun is anchored by the earliest flights after sunset, not by daytime EL, so whether a module at sunset is as fully recovered as at midday is an assumption; the flash I-⁠V benchmark of light-soaked sample modules tests it.
  • Drive current. The EL-to-power model[2] was validated at 6 A; the field data of this project were taken at 5 A. The model must be calibrated at the current used in the field.
  • Model form. Eq. (2) is empirical, has one time constant and is not derived from defect kinetics. The lab dark-storage series of[1] is better described by a fast (τ ≈ 1.3 h) and a slow (τ ≈ 13 h) component (QE analysis, one module), so a fitted τ depends on the time window. The field data cover up to about 6 h after sunset, and the curve is not intended for extrapolation beyond the survey window.
  • Status of evidence. This white paper has not been peer reviewed; [2] is in revision and [1] is a conference presentation. Field results come from one project.

Claim workflow · On a new project

  • Fly night EL plus dusk strings. Fly from dusk into the night at one drive current, recording the time after sunset of every flight; image 10 to 20 strings twice, at night and again within 30 min after sunset, to pin the drop and measure the share of dark cells that do not recover. A third pass on the same strings 5 to 8 h after sunset shows how far cells keep darkening later in the night.
  • Fit τ per project. Normalize with Eq. (1) and fit Eq. (2); check the taper band and depth factor of Eq. (3) on the paired cells; report r_sun, r_∞ and τ with the data set size and fit statistics.
  • Correct to daylight. Lift every night image to t′ = 0 with Eq. (3); check the correction by lifting to the dusk flight time and comparing cell by cell with the measured dusk images; report bias and per-cell scatter.
  • Calculate power loss per module from the corrected image with the EL-to-power method[2].
  • Validate the correction with lab EL. Take a sample of the surveyed modules to the lab, image them in the light-recovered state at the field drive current, and compare cell by cell with the same modules' field images corrected to t′ = 0 with Eq. (3). The agreement measures the accuracy of the correction itself, independent of the power model.
  • Benchmark with flash I-⁠V on the same sample in the light-recovered state, to check the EL-derived power.
  • Report permanent and recoverable parts, ΔP_perm and ΔP_rec(T) per module, Eq. (4), for comparison with nameplate and the warranted minimum power in the module's warranty.

Quantified Energy

Helping clients with UVID warranty claims.

Quantified Energy gives asset owners and their advisers the power each module loses in operation, measured at fleet scale and traceable to the lab.

2,000,000+ TOPCon modules measured by Quantified Energy

Power loss per module, in operation

The figure a warranty or insurance claim rests on, compared with nameplate and the warranted minimum power in the module’s warranty.

Ready to compare with nameplate and with the warranted minimum power, in a warranty or insurance claim.

Answer to “it recovers in sunlight”

Recoverable night loss separated from the permanent UVID loss, with τ measured per project. On one project, modules with 15% class cells fell from 2,396 on the night EL to 12 after correction to daylight (modeled).

The recoverable loss, which builds up at night and recovers in daylight, is separated from the permanent loss. The darkening curve and its τ are measured on each project. On one project, 2,396 modules showed very dark cells in the raw night images, but only 12 after correction to the daylight state (modeled).

Traceable to lab measurement

Benchmarked to flash I-⁠V on a sample of modules; EL-to-power method[2], dark-storage work with SERIS[1], quantitative EL since 2018[3].

Checked against power measured in the lab on a sample of modules; built on a published EL-to-power method[2], dark-storage work with SERIS[1] and quantitative EL since 2018[3].

Technical note How results are reported. Per module, Pmax in the daylight state is calculated in Step 6 with the degradation-mode EL-to-power method[2] from the image corrected to t′ = 0. The loss is split as in Eq. (4) into a permanent part, ΔP_perm, the loss in operation, and a recoverable part, ΔP_rec(T), the additional loss at the time T of the night flight. EL-derived power is benchmarked against flash I-⁠V of a sample of modules in the light-recovered state. The project curve is reported with r_sun, r_∞ and τ, the data set behind the fit (modules, strings, nights), fit statistics, and the result of the dusk-flight check on strings flown twice, stated as bias and per-cell scatter of the corrected dark-cell levels (on this project unbiased and about 6% of the bright level per cell, 580 modules). Warranty terms differ by manufacturer; the report supplies the measured loss for comparison with the warranted minimum power, and it is not legal advice or a prediction of a claim outcome.

Warranty terms differ by manufacturer. The report supplies the measured loss for comparison with the warranted minimum power; it is not legal advice or a prediction of a claim outcome.

Fly once from dusk into the night. Get the loss in operation.

Talk to us

References

  1. [1]A. Nairi, J. Wong, Y. S. Khoo, K. Bedrich, F. Lim, S. Nalluri, J. D. Arcebal, T. Reindl, A. G. Aberle, "Comparative study of four recovery methods and subsequent dark storage metastability in UV induced degradation (UVID) affected TOPCon PV modules," EU PVSEC 2026, September 15, 2026.
  2. [2]J. Wong, K. Bedrich, Y. S. Khoo, J. Chai, F. Lim, A. Nairi, Y. Wang, "Quantitative Electroluminescence Image Analysis for PV Modules: A Degradation-Mode Approach," IEEE Journal of Photovoltaics, in revision, 2026.
  3. [3]K. G. Bedrich, W. Luo, M. Pravettoni, D. Chen, Y. Chen, Z. Wang, P. J. Verlinden, P. Hacke, Z. Feng, J. Chai, Y. Wang, A. G. Aberle, Y. S. Khoo, "Quantitative electroluminescence imaging analysis for performance estimation of PID-influenced PV modules," IEEE Journal of Photovoltaics, vol. 8, no. 5, pp. 1281–1288, 2018.
  4. [4]VDMA, "International Technology Roadmap for Photovoltaic (ITRPV)," 17th edition, 2026.
  5. [5]Kiwa PVEL, "2026 PV Module Reliability Scorecard," UV-induced degradation (UVID) results, 2026.
  6. [6]InfoLink Consulting, "InfoLink 2025 global module shipment ranking: combined shipments reach 536 GW," February 2026.

Lab data: SERIS with Quantified Energy. Field data: Quantified Energy drone EL surveys, 2026.

Make every PV module count throughout its lifetime.